Specifications
Manifolds:
Maximum Inlet Pressure: 3000 psig
Delivery Pressure Range: 50–150 psig
(For higher delivery pressures, contact your
Advanced Representative)
Flow Coefficient (each station valve):
Brass Manifolds: Cv = 0.25
Stn. Stl. Manifolds: Cv = 0.30
Inlet Connections:
CGA connection as specified
Outlet Connection: 1/2" NPT female
Regulators:
Brass Systems: HPD-3-150
Stn. Stl. Systems: APC-3-150
Optional Pressure Switch
Optional Master Shut-off Valve: SG5475 Series
Ordering Information
To order a semi-automatic changeover manifold system, complete the part number using the "Part Number Key". For example, to order a 6 cylinder,brass
changeover system, with flexible pigtails, without check valves, and with CGA 350 connections, the part number would be AC-6BF-350. Order by complete part
number.
Note: Two cylinder semi-automatic manifolds do not include manifold headers. Cylinders are connected directly to the regulator
inlet pigtails (cylinder leads).
Manifolds for Acetylene Service require flashback arrestors (SG6545). All manifolds ordered with CGA 510 will be shipped with flashback arrestors installed
on each pigtail, unless the order specifies with which gas it will be used.
Warning: Advanced does not recommend the use of stainless steel manifolds for Oxygen service and will not provide such manifolds with CGA
540 connections.
|